Viessmann · Boiler troubleshooting
Rooms cold while burners are operating
What is going on
The heating is running but the rooms stay cold.
Likely causes
- Time incorrectly set
- Heating program 'w' or 9 is set
- DHW priority active (w shown in display) on systems with DHW tank only
- On/off switch on the mixing valve motor set to OFF
- Heating curve setting incorrect
- Control unit incorrectly programmed or set
Check in this order
- Set the correct time.
- Set the 'rw' heating program (see page 6).
- On DHW tank systems, wait until the tank has heated up; w goes off in the display.
- Turn the mixing valve motor on/off switch to I ON.
- Check and correct the heating curve setting if needed.
- Check and correct the temperature, time program and heating program settings if needed.
Applies to: Vitocontrol-S VD2/CT3/CM2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.