Viessmann · Boiler troubleshooting
Reinstall burner
What is going on
Refit the burner with the specified torques, then check the gas connection for tightness.
Check in this order
- Reconnect the fan motor cables, fit the burner and diagonally tighten the four Torx T-30 screws to 4 Nm (35 lb.in.).
- Fit the new supplied gasket and tighten the gas connection fitting to 15 Nm (132 lb.in.).
- Plug the Venturi extension into the fan.
- Reconnect the gas valve and electrode block cables.
- Open the gas shutoff valve and switch on power.
- Check the gas connection for tightness.
- Refit the front panel.
Applies to: Vitodens 100-W, WB1B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.