Weil-McLain · Boiler troubleshooting

Vertical concentric vent/air termination installation

SVF 500/600 Series 1

What is going on

Concentric roof termination with the air inlet around the vent pipe.

Check in this order

  1. Buy the concentric termination kit separately and make sure it is the approved kit.
  2. Cut a clearance hole for the termination outside diameter, following the kit instructions.
  3. Set a corrosion-resistant thimble in the vent hole and provide flashing and sealing boots sized for the termination outside diameter.
  4. Assemble the termination as described for concentric terminations, and cover the end with plastic before passing it through the roof to keep debris out.
  5. Position the termination so it stays 12 in min above roof or snow line and no more than 24 in above it (18 in min in Canada).
  6. Support the termination at the roof with supports or bracing that stop vertical slippage and sideways movement. Do not use clamps that cut into the pipe or have sharp edges.
  7. Connect piping from the boiler to the termination after the termination is in place and supported.
  8. Install the bird screen and rain cap only after the assembly is through the roof and all supports are attached, and cement the rain cap in place.
  9. Do not drill or screw into the vent or air pipe or fittings, and do not let the piping weight rest on the boiler fittings.
  10. Do not connect any other appliance to the vent pipe or join multiple boilers to a common vent.

Applies to: SVF direct vent vertical concentric (Category IV)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, pp. 52-53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.