Annual startup and maintenance schedule

SlimFit Series 2

What is going on

Service technician tasks for the annual startup, plus owner tasks that run daily, monthly, every six months and at end of season.

Check in this order

  1. Investigate any reported problems.
  2. Inspect and clean the air inlet box screen, and do not use solvents.
  3. Clean the base collector and condensate trap and refill with fresh water.
  4. Check for water, gas, flue and condensate leaks.
  5. Check water chemistry, inhibitor and antifreeze concentration.
  6. Check the boiler relief valve and expansion tank.
  7. Inspect the flue and air lines for condition and tightness.
  8. Inspect, clean and check spacing of the ignition electrode and flame sense rods.
  9. Check the high gas pressure switch, low gas pressure switch, low water cutoff, and operating and high limits.
  10. Run startup checkout and verify flame stability and flame signal.
  11. Clean the heat exchanger if flue temperature is more than 30 °F above return water temperature.
  12. Check blower speed settings.
  13. Owner daily check boiler area, air openings and pressure/temperature gauge.
  14. Owner monthly check vent piping, air piping, relief valve, condensate drain and automatic air vents.
  15. Owner periodically test the low water cutoff using the test button.
  16. Owner every six months check boiler piping for gas and water, and operate the relief valve.
  17. Owner at end of season shut the boiler down unless it supplies domestic hot water.

Applies to: SlimFit Series 2 annual service

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.