Weil-McLain · Boiler troubleshooting

Flow switch or combustion air damper interlock

Evergreen Series 2

What is going on

Proof of closure can be a flow switch or a CAD interlock. Both are wired through the J18 jumper location.

Check in this order

  1. Remove the jumper on J18 and wire the flow switch or CAD contacts in place of it, as shown in the wiring diagram.
  2. For a flow switch, no control settings are needed.
  3. For a CAD interlock, assign Input 3 as an AUX PUMP/OUTPUT, and select local or System Damper for the operating mode.
  4. Confirm the damper will open whenever the boiler is called to fire. Output 3 supplies 120VAC to the damper motor. Use an isolation relay for a different voltage or for loads above 2.0 A.
  5. On multi-boiler CAD interlocks, wire all proof of closure inputs in series with the end devices and each boiler's closure switch input.
  6. Use only electrically isolated contacts, since the J18 jumper circuit carries 5 VDC.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.