Pressure relief valve discharge piping
What is going on
No valve may be installed between the pressure relief valve and the boiler. Discharge piping must be sized and routed per the ASME code and drained safely.
Check in this order
- Do not install any valve between the relief valve and the boiler.
- Make the discharge pipe full size of the valve outlet, as short and straight as possible.
- Place any elbow close to the valve outlet.
- Route discharge so no one can be scalded and so the pipe can be drained.
- Keep the pipe size and layout so pressure cannot reduce relieving capacity.
Applies to: Boiler pressure relief valve piping
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 installation manual, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.