Weil-McLain · Boiler troubleshooting

Check water chemistry and inhibitor at least yearly

SlimFit Series 2

What is going on

Water and inhibitor are checked after fill and once a year to prevent corrosion.

Likely causes

  • Low pH or low inhibitor level
  • Antifreeze concentration too low

Check in this order

  1. After fill and leak test, check pH and chlorine.
  2. Verify antifreeze concentration if it is used.
  3. Test a water sample for pH. It must be 7.0 to 8.5, or use the Sentinel test kit to check inhibitor concentration.
  4. If pH is out of range or the test kit shows low inhibitor, correct it.
  5. Test antifreeze concentration at least annually. If it is low, add antifreeze or drain and refill with the correct mix.
  6. Check the inhibitor level again after any adjustment.

Applies to: SlimFit Series 2 annual maintenance

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.