Weil-McLain · Boiler troubleshooting
Check water chemistry and inhibitor at least yearly
What is going on
Water and inhibitor are checked after fill and once a year to prevent corrosion.
Likely causes
- Low pH or low inhibitor level
- Antifreeze concentration too low
Check in this order
- After fill and leak test, check pH and chlorine.
- Verify antifreeze concentration if it is used.
- Test a water sample for pH. It must be 7.0 to 8.5, or use the Sentinel test kit to check inhibitor concentration.
- If pH is out of range or the test kit shows low inhibitor, correct it.
- Test antifreeze concentration at least annually. If it is low, add antifreeze or drain and refill with the correct mix.
- Check the inhibitor level again after any adjustment.
Applies to: SlimFit Series 2 annual maintenance
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.