Connecting low water cut-off device

Vitotronic 100 GC1

What is going on

Wiring of an external low water cut-off into the control's safety circuit.

Check in this order

  1. Disconnect power to the control and burner.
  2. Remove the jumper between terminals 12 and 15.
  3. Connect the low water cut-off as shown in the diagram.
  4. Note aBH supplies 120 VAC power for accessories; aBÖ is the connection for external safety equipment at 120 VAC.

Applies to: Vitotronic 100 GC1 low water cut-off wiring

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.