Weil-McLain · Boiler troubleshooting

Seat boiler on wall-mount bracket

Ultra Series 4

What is going on

Use a reference line to confirm the boiler is fully engaged with the bracket.

Check in this order

  1. Mark a line 30-3/4 in. below the bottom edge of the bracket for Ultra-80 to -230, or 35-5/8 in. for Ultra-299 and -399.
  2. Remove the jacket front panel before lifting.
  3. Get help to lift the boiler above the bracket.
  4. Slide the rear of the boiler down against the lag screw heads.
  5. Confirm the bottom of the enclosure is at or near the reference line.
  6. If it does not reach the line, adjust until the brackets fully engage.

Applies to: Wall-mounted Ultra-80 through Ultra-399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.