Seat boiler on wall-mount bracket
What is going on
Use a reference line to confirm the boiler is fully engaged with the bracket.
Check in this order
- Mark a line 30-3/4 in. below the bottom edge of the bracket for Ultra-80 to -230, or 35-5/8 in. for Ultra-299 and -399.
- Remove the jacket front panel before lifting.
- Get help to lift the boiler above the bracket.
- Slide the rear of the boiler down against the lag screw heads.
- Confirm the bottom of the enclosure is at or near the reference line.
- If it does not reach the line, adjust until the brackets fully engage.
Applies to: Wall-mounted Ultra-80 through Ultra-399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.