Viessmann · Boiler troubleshooting

Vitodens 200 WB2B with Vitotronic 200 HO1 communication wiring and outdoor sensor

Versatronik 300 Cascade Control

What is going on

Same CAT5e non-crossover LON cable. The outdoor sensor must be connected or an outdoor sensor fault will always show.

Likely causes

  • Outdoor temperature sensor not connected to the boiler control

Check in this order

  1. Plug the cable into the J1 receptacle in the upper right of the control board.
  2. Connect the CAT5e cable to the boiler control LON communication boards.
  3. Connect the outdoor temperature sensor. It can be mounted inside the boiler housing.
  4. If a sensor cannot be fitted, use a resistor to simulate an outdoor temperature above 20 C / 68 F.

Applies to: Vitodens 200 WB2B with Vitotronic 200 HO1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.