Vitodens 200 WB2B with Vitotronic 200 HO1 communication wiring and outdoor sensor
What is going on
Same CAT5e non-crossover LON cable. The outdoor sensor must be connected or an outdoor sensor fault will always show.
Likely causes
- Outdoor temperature sensor not connected to the boiler control
Check in this order
- Plug the cable into the J1 receptacle in the upper right of the control board.
- Connect the CAT5e cable to the boiler control LON communication boards.
- Connect the outdoor temperature sensor. It can be mounted inside the boiler housing.
- If a sensor cannot be fitted, use a resistor to simulate an outdoor temperature above 20 C / 68 F.
Applies to: Vitodens 200 WB2B with Vitotronic 200 HO1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.