Viessmann · Boiler troubleshooting
Fixed high limit test, method 1 (CSD-1)
What is going on
Simulates an over-temperature to check the fixed high limit. Only do this where required by law. The manufacturer is not responsible for damage caused by overheating the system during this test.
Check in this order
- Confirm the boiler and boiler pump are in normal working condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- Open the extended menu and select test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go into high fire.
- Once the burner is lit, carefully unplug the boiler pump plug from the control board.
- Watch the boiler temperature rise until the burner shuts off.
- Keep watching. The boiler should reach 210 F (99 C), where the manual reset high limit trips and shows fault F2.
- If the limit is not reached, wait two minutes after burner shutoff, then plug the boiler pump in for no more than 1 second. Repeat as needed.
Applies to: Vitodens 200-W B2HA 112/150/399/530 (boiler sizes with flow switches may need the switches jumpered)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.