Weil-McLain · Boiler troubleshooting
Hydrostatic pressure test before gas and electrical hookup
What is going on
Test the boiler with water before connecting gas piping or power. Use a test gauge of the right range, not the gauge shipped with the boiler. Steam boilers are tested at 45 to 55 psi. Water boilers are tested at 1-1/2 times maximum working pressure.
Likely causes
- Leaks in the boiler or tappings
- Petroleum-based sealing compounds, which damage the boiler
Check in this order
- Plug any boiler tappings or openings not in use.
- Install a test gauge with an appropriate range.
- Fill the boiler with water and vent all air.
- Pressurize to 45 to 55 psi for a steam boiler, or 1-1/2 times maximum working pressure for a water boiler.
- Do not leave the boiler unattended during the test.
- Confirm the gauge holds pressure and check all joints for leaks.
- Drain the boiler, repair any leaks at once and retest.
- Remove plugs from tappings that will carry controls and accessories.
- On first startup, check the system piping for leaks and repair at once.
Applies to: EG and PEG boilers, pre-startup
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.