Weil-McLain · Boiler troubleshooting

Hydrostatic pressure test before gas and electrical hookup

EGPEG

What is going on

Test the boiler with water before connecting gas piping or power. Use a test gauge of the right range, not the gauge shipped with the boiler. Steam boilers are tested at 45 to 55 psi. Water boilers are tested at 1-1/2 times maximum working pressure.

Likely causes

  • Leaks in the boiler or tappings
  • Petroleum-based sealing compounds, which damage the boiler

Check in this order

  1. Plug any boiler tappings or openings not in use.
  2. Install a test gauge with an appropriate range.
  3. Fill the boiler with water and vent all air.
  4. Pressurize to 45 to 55 psi for a steam boiler, or 1-1/2 times maximum working pressure for a water boiler.
  5. Do not leave the boiler unattended during the test.
  6. Confirm the gauge holds pressure and check all joints for leaks.
  7. Drain the boiler, repair any leaks at once and retest.
  8. Remove plugs from tappings that will carry controls and accessories.
  9. On first startup, check the system piping for leaks and repair at once.

Applies to: EG and PEG boilers, pre-startup

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.