Viessmann · Boiler troubleshooting
System version 7 design: three-way mixing valve with several heating circuits
What is going on
Lead boiler is a Vitocrossal 300 with lag Vitorond 200 boilers, run by an outdoor-reset control with modulating boiler water temperature and load-based sequencing. Heating circuits with higher return temperature go to the upper return connection, lower ones to the lower return connection. At least 15% of rated output must go to the lower return connection. Sensor T1 reads the return temperature and the boiler control holds the mixing valve so the return never drops below minimum. Boiler supply temperature follows the highest mixing circuit demand plus an adjustable differential. Intended for heating circuits with temperature differentials of 20 °C / 68 °F or more.
Check in this order
- Connect at least 15% of rated output to the lower return connection.
- Connect the T1 return sensor so it reads the return temperature.
- Verify the connection diagram on site for completeness and function, since it is only a recommendation.
- Use field-supplied motor contactors or starters for single-phase and three-phase pumps.
Applies to: System version 7
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 24-26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.