Weil-McLain · Boiler troubleshooting

Servicing the domestic water outlet manifold (heating cartridge and sanitary shutter)

ECO Tec Series 3

What is going on

Clean and inspect the cartridge and shutter, replace worn O-rings and reassemble with the torque values in the torque table.

Likely causes

  • Worn or damaged valve shutter, springs or seats

Check in this order

  1. Follow the gas and electrical shut-off steps and the brazed plate steps 1 through 6 on page 156.
  2. Slide the actuator retaining clip out of its slot and remove the actuator, keeping its wire attached.
  3. Remove the spacer with a 28mm (1 1/8 in) wrench, which takes the sanitary shutter with it.
  4. Remove the heating cartridge with a 22mm (7/8 in) wrench.
  5. Clean the cartridge and shutter. Compress the springs to check them. Replace any damaged or heavily worn parts.
  6. Check both O-rings and seats. Replace O-rings if needed, clean the seats and lightly grease with non-petroleum grease.
  7. Grease the tip of the shutter rod and reassemble it with the spacer. Put it in the outlet manifold without tightening.
  8. Screw the heating cartridge in and torque to the value in the torque table.
  9. Tighten the spacer to the value in the torque table.
  10. Reinstall the actuator and retaining clip.
  11. The DHW temperature sensor is in this manifold. Verify it using the temperature sensor check.
  12. Open the CH supply and return valves, refill the boiler, purge air and check all joints for leaks.

Applies to: 80/110/150/199 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 158. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.