Servicing the domestic water outlet manifold (heating cartridge and sanitary shutter)
What is going on
Clean and inspect the cartridge and shutter, replace worn O-rings and reassemble with the torque values in the torque table.
Likely causes
- Worn or damaged valve shutter, springs or seats
Check in this order
- Follow the gas and electrical shut-off steps and the brazed plate steps 1 through 6 on page 156.
- Slide the actuator retaining clip out of its slot and remove the actuator, keeping its wire attached.
- Remove the spacer with a 28mm (1 1/8 in) wrench, which takes the sanitary shutter with it.
- Remove the heating cartridge with a 22mm (7/8 in) wrench.
- Clean the cartridge and shutter. Compress the springs to check them. Replace any damaged or heavily worn parts.
- Check both O-rings and seats. Replace O-rings if needed, clean the seats and lightly grease with non-petroleum grease.
- Grease the tip of the shutter rod and reassemble it with the spacer. Put it in the outlet manifold without tightening.
- Screw the heating cartridge in and torque to the value in the torque table.
- Tighten the spacer to the value in the torque table.
- Reinstall the actuator and retaining clip.
- The DHW temperature sensor is in this manifold. Verify it using the temperature sensor check.
- Open the CH supply and return valves, refill the boiler, purge air and check all joints for leaks.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 158. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.