Boiler needs make-up water often, popping noise or black water

Weil-McLain WTGO Series 4

What is going on

Make-up water keeps going into the boiler. Fresh water brings in minerals and oxygen, which cause popping/percolating noise in the sections (lime) and black water (oxygen corrosion).

Likely causes

  • Leak in the boiler or piping
  • Lime build-up in the sections from constant make-up water
  • Boiler water pH out of range
  • Oxygen corrosion from leaks

Check in this order

  1. Find and repair leaks in the boiler and piping right away. That stops the make-up water.
  2. Check boiler water pH. It should be 7.0 to 8.5.
  3. If the boiler pops or percolates, de-lime the boiler after the leaks are fixed.
  4. Black water means corrosion fix the leaks and correct the pH.

Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting, p.7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.