Weil-McLain · Boiler troubleshooting
Boiler needs make-up water often, popping noise or black water
What is going on
Make-up water keeps going into the boiler. Fresh water brings in minerals and oxygen, which cause popping/percolating noise in the sections (lime) and black water (oxygen corrosion).
Likely causes
- Leak in the boiler or piping
- Lime build-up in the sections from constant make-up water
- Boiler water pH out of range
- Oxygen corrosion from leaks
Check in this order
- Find and repair leaks in the boiler and piping right away. That stops the make-up water.
- Check boiler water pH. It should be 7.0 to 8.5.
- If the boiler pops or percolates, de-lime the boiler after the leaks are fixed.
- Black water means corrosion fix the leaks and correct the pH.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting, p.7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.