Viessmann · Boiler troubleshooting
Fill and pressurise the heating system
What is going on
Set the expansion vessel precharge first, then fill and vent the system at the correct pressure.
Check in this order
- With the system cold, check the expansion vessel precharge. If it is lower than the static system pressure, top it up with nitrogen until it is 1.5 to 3 psi (0.1 to 0.2 bar) above static pressure.
- Close the gas shutoff valve.
- Open any installed shutoff valves.
- Fill the heating system with water and vent it, until the fill pressure is 1.5 to 3 psi (0.1 to 0.2 bar) above the vessel precharge, using the boiler drain/fill valve.
- Mark the set pressure on the temperature and pressure gauge.
- Record the fill volume, water hardness and pH value.
- Return the shutoff valves to their operating position.
- Close the boiler drain/fill valve.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.