Weil-McLain · Boiler troubleshooting

Nuisance shutdowns: check system grounding

EG / PEG Series 7

What is going on

Chart 4. The pilot assembly and ignition control must share a common ground with the main burner. Poor or erratic ground commonly causes nuisance shutdowns.

Likely causes

  • Poor metal-to-metal contact at pilot bracket, main burner or burner rest
  • Loose or damaged ground lead at ignition control or transformer
  • Damaged ground wire

Check in this order

  1. Turn off power before working on the controls.
  2. Check for good metal-to-metal contact between the pilot burner bracket and the main burner, and between the main burner and the burner rest.
  3. Check the ground lead from the GND (Burner) terminal on the ignition control to the ignition control mounting screw.
  4. Check the ground lead from the C terminal on the transformer to the transformer case ground.
  5. Make sure all connections are clean and tight.
  6. If a wire is damaged or deteriorated, replace it with 18 gauge moisture-resistant thermoplastic wire rated 105°C minimum.

Applies to: EG and PEG Series 7 boilers with pilot ignition

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.