Weil-McLain · Boiler troubleshooting
Nuisance shutdowns: check system grounding
What is going on
Chart 4. The pilot assembly and ignition control must share a common ground with the main burner. Poor or erratic ground commonly causes nuisance shutdowns.
Likely causes
- Poor metal-to-metal contact at pilot bracket, main burner or burner rest
- Loose or damaged ground lead at ignition control or transformer
- Damaged ground wire
Check in this order
- Turn off power before working on the controls.
- Check for good metal-to-metal contact between the pilot burner bracket and the main burner, and between the main burner and the burner rest.
- Check the ground lead from the GND (Burner) terminal on the ignition control to the ignition control mounting screw.
- Check the ground lead from the C terminal on the transformer to the transformer case ground.
- Make sure all connections are clean and tight.
- If a wire is damaged or deteriorated, replace it with 18 gauge moisture-resistant thermoplastic wire rated 105°C minimum.
Applies to: EG and PEG Series 7 boilers with pilot ignition
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG/PEG Series 7 boiler manual, p. 81. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.