Weil-McLain · Boiler troubleshooting
Schematic wiring diagram: connector and sensor reference
What is going on
Reference for the factory and field connections on the schematic. Connections shown include the power inputs, circulators, gas valve, flame and spark, and optional sensors and contacts.
Check in this order
- Use the schematic to locate J12 (Modbus), J13/J14 (touch screen), J15 (flue air pressure switch), J16 (0-10 VDC inputs and outputs), J17 (thermostat inputs), J18 (proof of closure), and J22 (boiler inlet temperature sensor).
- Check the outdoor air temperature sensor, system supply and return sensors, and additional heat demand contacts at the J16 and J17 blocks if used.
- Check the additional limits one requires manual reset, the other resets automatically.
- Note that factory installed jumpers must be removed if an external device is used.
- Verify the spark and flame sense electrode wiring at J7/J8 and the gas valve at J3/J4.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 79. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.