Weil-McLain · Boiler troubleshooting

ECO Tec S2 does not light: 5 tries then 60 minute wait

Weil-McLain ECO Tec Series 2

What is going on

If no flame is proven, the control shuts the gas valve, post-purges and tries again. After 5 failed tries it waits 60 minutes before trying again.

Likely causes

  • Gas off or low inlet pressure
  • Gas valve throttle/offset out of adjustment (often after a conversion)
  • Ignition electrode / flame sensor worn, dirty or gap wrong
  • Blocked vent or air intake
  • Condensate backed up

Check in this order

  1. Power off and gas off before opening the boiler.
  2. Check gas is on and inlet pressure is right at the gas valve inlet test port.
  3. Check vent and air pipes for blockage, and that the condensate trap and drain are clear.
  4. Inspect the ignition electrode / flame sensor and its wire.
  5. If the boiler was just converted, check the gas valve coarse settings (see the gas conversion guide).
  6. Reset the control from the display and watch the light-off: pre-purge, spark, then flame check.

Applies to: ECO Tec 80/110/150/199 Series 2 heating only

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Sequence of operation Figure 72 p.74. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.