Skim a new steam boiler to remove oil and grease
What is going on
Clean newly installed steam boilers to remove oil and grease. Failure to clean can cause violent water level changes, water entering steam mains and high maintenance on strainers, traps and vents. Do not use petroleum-based compounds.
Check in this order
- Provide 1-1/2 in. piping from the skim tapping to a floor drain.
- Adjust the waterline to the midpoint of the skim tapping (see Figure 4, page 14).
- Fire the boiler to keep temperature below the steaming rate, following the lighting instructions.
- Feed in water to maintain water level and cycle burners to prevent steam pressure rise.
- Continue skimming until discharge is clear; this may take several hours.
- Drain the boiler; while warm but not hot, flush all interior surfaces under full pressure until drain water runs clear.
- Remove skim piping and plug the tapping.
- Close the drain cock, fill with fresh water to the waterline, then start burners and steam for 15 minutes to remove dissolved gases. Stop burners.
- Check traps and air vents for proper operation.
- Repeat the process after several weeks of operation if needed.
Applies to: New EG / PEG steam boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 boiler manual, p. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.