Viessmann · Boiler troubleshooting
Replace plug console with relay
What is going on
Plug console that carries the relay contactor.
Check in this order
- Unplug plugs 40/156 and 40 from the back of the plug console.
- Disconnect the two yellow/green ground wires from the terminal block below the console.
- Disconnect wires T1 (brown) and T2 (blue) from the relay contactor.
- Remove the four 3 mm hex head screws and washers from the mounting plate.
- Fit the new plug console with relay.
- Reassemble in reverse order.
Applies to: Plug console with relay
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.