Weil-McLain · Boiler troubleshooting

Closure switch (flow switch or CAD) lockout

SVF Series 1

What is going on

A flow switch or combustion air damper interlock must make before the blower runs. The control allows four minutes for the switch to make, and a lockout occurs if it does not, or if it opens during firing.

Likely causes

  • Closure switch not made within four minutes of a call for heat
  • Closure switch opens while the burner is firing
  • Shared end switch not verifying the damper or louver

Check in this order

  1. Confirm the closure switch is an isolated contact.
  2. For a CAD on one boiler, assign INPUT 3 as AUX PUMP/OUTPUT and select Damper Control.
  3. For a shared end switch, assign INPUT 2 as AUX PUMP/OUTPUT and select ANY Burner Demand.
  4. Check that the damper or louver opens and the switch closes within four minutes of the call.
  5. If the switch opened during firing, check the interlock device for intermittent operation.
  6. The lockout clears automatically once the closure switch makes.

Applies to: Flow switch or CAD interlock on Input 2 or Input 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, pp. 62-63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.