What is going on

Use this when DHW flow is higher than the boiler allows or the DHW coil has high pressure drop. DHW flows only through the secondary connection piping.

Check in this order

  1. Size the secondary connection piping (no more than 8 pipe diameters apart) for the full DHW flow.
  2. Install a system circulator sized for the required flow and head.
  3. Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
  4. Size the boiler loop piping at least to the minimum in the pipe sizing table.
  5. Do not use a closed-type tank if the water heater has an automatic vent.
  6. Use the Advanced Manual to set the boiler pump to run during DHW demand, if needed. DHW as a zone does not apply to this setup.

Applies to: High flow DHW circuits

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 550/750 Series 3 boiler manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.