Viessmann · Boiler troubleshooting
Bleed air from boiler heat exchanger
What is going on
Purge air from the boiler heat exchanger by flushing it through the boiler supply and return with isolation valves closed.
Check in this order
- Connect a hose from the boiler filling tap to a fresh water supply or heating medium.
- Open the fresh water supply valve, then open the boiler filling tap slowly. Keep isolation valves closed.
- Flush the heat exchanger through supply and return for at least 10 minutes until all air is removed.
- When the drain valve runs water, close the boiler drain valve, then the boiler fill valve, and open the system isolation valves.
- Close the gas shut-off valve and switch the control unit ON.
- Run the venting program from the service menu.
- Check system pressure.
- Confirm adequate fuel supply, then open the gas shut-off valve.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.