Viessmann · Boiler troubleshooting
Checking the flue gas flapper
What is going on
Back flue gas flapper in the burner mixing shaft. Check the damper and gasket for dirt or damage.
Check in this order
- Undo the 2 screws and remove the fan.
- Remove the flue gas flapper.
- Check the damper and gasket for dirt and damage, and replace if needed.
- Refit the flapper with the correct installation position.
- Refit the fan and secure with 2 screws to 35 lb.in (4.0 Nm).
Applies to: B1HE/KE 85/120 and 150/199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.