Direct exhaust vertical termination installation
What is going on
Category IV direct exhaust through the roof or a vertical termination. Same material and joint rules as the sidewall method. Use flashing and sealing boots sized for the vent pipe. Do not exceed the maximum outside vent length shown in Figure 30, because excess exposed pipe can freeze condensate or cause failure.
Likely causes
- Condensate freezing in the vent pipe if too much pipe is exposed outside
- Vent/air piping failure in very cold climates
Check in this order
- Install the vent manufacturer's SlimFit Vent Adapter and reducer (if needed) at the boiler vent connection.
- Slope vent piping toward the boiler at least 1/4 in per foot on horizontal runs.
- Support piping every 5 ft on horizontal and vertical runs, with a hanger within 6 in of any upturn.
- Cut the vent penetration. For combustible construction, make it at least 3/8 in larger than the pipe diameter.
- Install a corrosion-resistant metal thimble and isolate the pipe per local code through floors, ceilings and roofs.
- Install flashing and sealing boots sized for the vent pipe.
- Use a coupling or open-end pipe termination per the vent manufacturer's vertical termination guidelines.
- Install a bird screen in the open end of the termination.
- Keep the finished termination dimensions as shown in Figure 30.
- Protect and support exposed piping per the vent manufacturer for cold climates.
Applies to: SlimFit 1000-2000 Series 2 direct exhaust, vertical
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit-1000-2000 Boiler Manual 550-100-561/1225, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.