Viessmann · Boiler troubleshooting

Alarm output (dry contact) activated

Vitotronic 100

What is going on

The control has a dry contact alarm output rated 24 VAC/DC, 1 FLA. It closes for any of the faults below and clears automatically when the fault is corrected.

Likely causes

  • Outdoor sensor failure (open)
  • Outdoor sensor failure (short)
  • Boiler sensor failure (open)
  • Boiler sensor failure (short)
  • DHW sensor failure (open)
  • DHW sensor failure (short)
  • Burner fault
  • LON communication failure (after 20 min.)

Check in this order

  1. Check the outdoor, boiler and DHW sensor wiring and sensor resistance for open or short faults.
  2. Check the burner for a fault condition.
  3. Check the LON communication wiring if the LON fault is present.
  4. Confirm the alarm clears once the fault is corrected.

Applies to: Vitotronic 100 KW10B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 KW10B installation manual, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.