Weil-McLain · Boiler troubleshooting

Hydrostatic pressure test before connecting water, gas or power

SlimFit Series 2

What is going on

Pressure test the boiler before permanent water or gas piping and electrical connections. Test pressure is 1½ times the relief valve setting. Examples: 45 PSIG for a 30 PSIG valve, 75 PSIG for a 50 PSIG valve, 150 PSIG for a 100 PSIG valve.

Check in this order

  1. Attach a 3-inch ANSI blind flange with a tapping for a nipple and valve to both the supply and return flanges, using pipe dope sparingly.
  2. Attach a water supply and hand pump to the lower valves, and a drain line to the upper valve.
  3. Remove the P/T gauge from the trim box and remove the factory plug from the ½-inch tapping on top of the boiler supply pipe.
  4. Install the P/T gauge in the ¼-inch tapping. Use a different gauge if the test pressure exceeds the gauge range.
  5. Open the supply and return shutoff valves and let water enter from the bottom and air exit at the top until all air is out of the heat exchanger. Then close the upper valve.
  6. Close the water supply and use the hand pump to raise pressure to the test value.
  7. Hold the test pressure for 10 minutes without leaving the boiler unattended, and confirm the gauge pressure stays constant.
  8. Check for leaks and repair them immediately.
  9. Disconnect the fill hose, open the upper valve, drain through the lower valve, and remove the test flanges and valve assemblies.

Applies to: SlimFit 1000-2000 Series 2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 12-13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.