Display blank but boiler operating

Ultra Series 4

What is going on

Communication lost between the U-Control and the display.

Likely causes

  • Loose connection or poor pin engagement at plug P9 or the display board
  • Broken wire in the harness from display to U-Control
  • Failed display module

Check in this order

  1. Check plug P9 on the U-Control and the back of the display board for loose connections and proper pin alignment.
  2. Check continuity on the wire harness from the display to the U-Control.
  3. Cycle power using the boiler power switch and check operation.
  4. If still faulty, replace the display module (see repair parts section).

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 119. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.