Weil-McLain · Boiler troubleshooting
Display blank but boiler operating
What is going on
Communication lost between the U-Control and the display.
Likely causes
- Loose connection or poor pin engagement at plug P9 or the display board
- Broken wire in the harness from display to U-Control
- Failed display module
Check in this order
- Check plug P9 on the U-Control and the back of the display board for loose connections and proper pin alignment.
- Check continuity on the wire harness from the display to the U-Control.
- Cycle power using the boiler power switch and check operation.
- If still faulty, replace the display module (see repair parts section).
Applies to: Ultra 80, 105, 155, 230, 299, 399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 119. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.