Viessmann · Boiler troubleshooting

Wiring the room controller to Viessmann Vitodens 100-W, WB1A

Versatronik

What is going on

The 4-pole plug on the boiler control provides the connection. The OT communication wires go to terminals 1 and 2 on the controller sub-base and are not polarity sensitive. If the 4-pole plug is missing from the boiler, get a replacement from the boiler supplier.

Check in this order

  1. Turn the boiler control down as described in the boiler manual.
  2. Find the 4-pole plug in the upper left corner on the back of the control.
  3. Wire the field cable into the 4-terminal plug at terminals 3 and 4.
  4. Run the field wire from the boiler to the controller.
  5. Connect the two communication wires to terminals 1 and 2 on the controller sub-base.

Applies to: Vitodens 100-W WB1A

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik COMO OT manual, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.