Weil-McLain · Boiler troubleshooting
Piping with refrigeration (chilled water) systems
What is going on
Chilled water must not enter the boiler. Cold water circulating through the boiler can damage the heat exchanger.
Likely causes
- Chilled medium entering the boiler
- Gravity circulation during cooling cycles
Check in this order
- Pipe the boiler in parallel with the chilled medium.
- Use valves to keep chilled medium out of the boiler (see Figure 18 for balancing and check valve layout).
- Where heating coils sit in air handlers exposed to refrigerated air, use flow control valves or other automatic means to stop gravity circulation during cooling.
Applies to: Boilers used with refrigeration systems
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG/PEG Series 7 boiler manual, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.