Viessmann · Boiler troubleshooting

Underfloor heating limit aquastat and electronic limits

Vitotronic 200

What is going on

The control's electronic high limit does not replace a separate limit aquastat required for underfloor heating. The aquastat switches the heating circuit pump off when supply temperature exceeds its set value. Supply temperature then cools slowly, so automatic reset can take several hours. Electronic limits are set with coding C6 (high) and C5 (low), both with a range of 34 to 262 F / 1 to 127 C.

Check in this order

  1. Install a limit aquastat for underfloor heating systems.
  2. Set the electronic max limit with coding C6 and the min limit with coding C5.
  3. Allow several hours for automatic reset after the aquastat trips.

Applies to: Underfloor heating

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 KW2 service instructions, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.