Cascade strategy: gross calorific (coding 3C: 0)

Vitocontrol-S VD2/CT3/CM2

What is going on

Operates as many boilers as possible at the lowest output for the best condensing effect. Gives long burner run times. Boilers are started by output statement and shut down by shutdown integral.

Check in this order

  1. Start-up a boiler starts (coding 3d: 1) when the current output can also be reached by the active boiler plus the next boiler in the sequence.
  2. Shutdown the shutdown integral must exceed the limit set in coding 46, then the last boiler started is shut down.

Applies to: Vitocontrol-S VD2/CT3/CM2 cascade, sequential control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 126. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.