Viessmann · Boiler troubleshooting
Lag boilers lose contact with lead boiler (cascade)
What is going on
After about 60 s of lost communication each boiler switches to emergency operation with its own flow setpoint.
Likely causes
- CAN bus break between lead and lag boilers
Check in this order
- Check CAN bus cables and plugs.
- Emergency setpoint is set with parameter 2451 (disabled by default; default 60 C / 140 F, range 0 to 80 C / 32 to 176 F).
- Frost protection stays active below 5 C (41 F).
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), p.13, 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.