Viessmann · Boiler troubleshooting

Lag boilers lose contact with lead boiler (cascade)

What is going on

On a Vitodens 200-W B2HE (85, 120, 150, 199) cascade, the lag boilers lose contact with the lead boiler. What you usually see is that after about 60 s of lost communication each boiler drops into emergency operation with its own flow setpoint, so the system keeps heating but not as one coordinated unit. Look at the CAN bus first, since a bad plug is the usual culprit.

Likely causes

  • CAN bus break between the lead and lag boilers, from a damaged cable or loose plug

Check in this order

  1. Check the CAN bus cables and plugs between the boilers, with power off when reseating connectors.
  2. The emergency setpoint is set with parameter 2451. It is disabled by default; default 60 C / 140 F, range 0 to 80 C / 32 to 176 F.
  3. Frost protection stays active below 5 C (41 F).
  4. After repairing the bus, confirm the lag boilers show communication with the lead again.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), p.13, 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.