Weil-McLain · Boiler troubleshooting
Boiler will not light / repeated ignition failure
What is going on
The control retries ignition after a failed flame check. After five failures it locks out for 60 minutes. Display banner turns red on an error or limit event.
Likely causes
- No flame signal at the electrode after ignition
- Gas supply or gas valve problem
- Error or limit event
Check in this order
- Watch the display banner. Red means an error or limit event.
- Let the 60 minute lockout run, or record the time of the failures.
- Check the gas supply and the gas valve.
- Check the electrode and flame signal.
- Check the flue and combustion air paths are clear.
Applies to: Evergreen Series 2 control
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.