Viessmann · Boiler troubleshooting

Connect the control unit to the Viessmann 2-wire BUS system

Vitotronic 200-H

What is going on

Set the BUS address and matching coding when the control shares a system with a boiler control or other Vitotronic.

Check in this order

  1. Plug in the Viessmann 2-wire BUS communication module (accessory; see parts list).
  2. Set the rotary dial on the communication module to a value between 4 and C that matches the system version.
  3. Do not set the rotary dial to the same value as another control unit.
  4. On a wall-mounted boiler with an actuator kit (Part No. 7133 392) for one mixing valve controller, the default rotary dial position is 4. Do not duplicate 4 when adding a second Vitotronic 200-H.
  5. With a boiler control for wall-mounted boilers or a Dekamatik system, adjust the differential temperature at that control.
  6. On the Vitotronic 200-H, set coding 9F to 0.
  7. If the outdoor temperature comes from a sensor already connected, set coding 97 to 1.

Applies to: Vitotronic 200-H on Viessmann 2-wire BUS

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.