Viessmann · Boiler troubleshooting
Outdoor sensor fault appears on Vitodens if sensor is missing
What is going on
An outdoor temperature sensor fault will always show on the boiler if the sensor is not connected. A resistor can be used in place of the sensor to fake a warm outdoor temperature.
Likely causes
- Outdoor temperature sensor not connected to the boiler control
Check in this order
- Connect the outdoor temperature sensor inside the boiler housing.
- If no sensor is used, fit a 10 kOhm resistor (brown-black-orange) in its place.
- Expect this resistor to read about 77F/25C, which is above the 68F/20C threshold.
Applies to: Vitodens 200 WB2B and B2HA
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control V1.4 manual, p. 16-17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.