Weil-McLain · Boiler troubleshooting
Gas-tight leak check at high fire
What is going on
The system must be sealed gas-tight to prevent flue gas spillage and CO. Leaks show as vapor on the inspection mirror.
Likely causes
- Loose cover plate joint
- Damaged gasket
- Loose condensate dish or vent adapter joint
- Vent piping seal failure
Check in this order
- Run the boiler at high fire.
- Move an inspection mirror around all heat exchanger cover plate joints at the top of the boiler.
- Check the joints between the condensate dish, vent adapter and vent pipe.
- Check every connection and seam of air and vent piping for gas-tight seals.
- If a leak is found, shut the boiler down immediately.
- Tighten the retaining screws or nuts if possible. Do not overtighten.
- If tightening does not fix it, disassemble the leaking component (see Maintenance section, page 103).
- Inspect gaskets and replace any that are damaged.
- Contact WM Technologies Technical Services if the problem is not solved.
Applies to: Heat exchanger cover plate, condensate dish, vent and air piping
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 100-101. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.