Weil-McLain · Boiler troubleshooting

Gas-tight leak check at high fire

SVF 500/600 Series 1

What is going on

The system must be sealed gas-tight to prevent flue gas spillage and CO. Leaks show as vapor on the inspection mirror.

Likely causes

  • Loose cover plate joint
  • Damaged gasket
  • Loose condensate dish or vent adapter joint
  • Vent piping seal failure

Check in this order

  1. Run the boiler at high fire.
  2. Move an inspection mirror around all heat exchanger cover plate joints at the top of the boiler.
  3. Check the joints between the condensate dish, vent adapter and vent pipe.
  4. Check every connection and seam of air and vent piping for gas-tight seals.
  5. If a leak is found, shut the boiler down immediately.
  6. Tighten the retaining screws or nuts if possible. Do not overtighten.
  7. If tightening does not fix it, disassemble the leaking component (see Maintenance section, page 103).
  8. Inspect gaskets and replace any that are damaged.
  9. Contact WM Technologies Technical Services if the problem is not solved.

Applies to: Heat exchanger cover plate, condensate dish, vent and air piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 100-101. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.