Weil-McLain · Boiler troubleshooting

Check flue gas temperature at high fire

Ultra Series 4

What is going on

Flue gas temperature at high fire should be no more than 54 °F above boiler return temperature.

Likely causes

  • Fouled Nanogate-coated heat exchanger

Check in this order

  1. Set the boiler to high fire.
  2. On the U-Control display, view flue gas temperature and boiler return temperature.
  3. Confirm flue gas is no more than 54 °F above return.
  4. If it is higher, shut down and let the boiler cool, then clean the Nanogate-coated heat exchanger (procedure starting on page 125).

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 113. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.