Weil-McLain · Boiler troubleshooting
Check flue gas temperature at high fire
What is going on
Flue gas temperature at high fire should be no more than 54 °F above boiler return temperature.
Likely causes
- Fouled Nanogate-coated heat exchanger
Check in this order
- Set the boiler to high fire.
- On the U-Control display, view flue gas temperature and boiler return temperature.
- Confirm flue gas is no more than 54 °F above return.
- If it is higher, shut down and let the boiler cool, then clean the Nanogate-coated heat exchanger (procedure starting on page 125).
Applies to: Ultra 80, 105, 155, 230, 299, 399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 113. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.