Viessmann · Boiler troubleshooting

Mixing valve motor direction check

Vitotronic 300

What is going on

During the actuator test, the supply temperature must rise when the mixing valve opens. If it drops, the motor is turning the wrong way or the mixing valve set is fitted incorrectly.

Likely causes

  • Motor turning in the wrong direction
  • Mixing valve set fitted incorrectly

Check in this order

  1. Run the actuator test and open the mixing valve.
  2. Watch the supply temperature.
  3. If it falls, check the motor direction and the mixing valve fitting against the mixing valve installation instructions.

Applies to: Mixing valve circuits HC2 and HC3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.