Viessmann · Boiler troubleshooting

Change rotational direction of mixing valve motor

Vitotronic 200

What is going on

Set the motor's rotation direction to suit the piping layout. The motor is delivered wired for the standard examples, so only change the wiring if the installation example needs it.

Check in this order

  1. Unscrew the motor cover.
  2. Turn the motor 180° and reconnect the connector.
  3. Check the wiring against the installation example (marker notch, HR heating return, HS heating supply, BR boiler return, BS boiler supply).
  4. Do not change the connections if the installation matches the delivered wiring.

Applies to: Vitotronic 200 KW2 mixing valve motor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 service instructions, pp. 73-74. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.