Weil-McLain · Boiler troubleshooting
Direct exhaust sidewall termination location and length
What is going on
Keep the vent exit where condensate, vapor and flue plume will not cause damage, injury or nuisance, and keep outside vent length within limits to avoid freezing.
Likely causes
- Outside vent length too long, condensate freezes and shuts the boiler down
- Termination above a door, window or deck
- Termination over a public walkway
Check in this order
- Use a down-turned elbow that butts against the outside wall plate.
- Keep the total vent piping within the maximum length in Figure 12 (allows 2 elbows; reduce for more elbows).
- Keep exposed outside pipe to 4 feet or less without an enclosure; longer runs need an enclosure that the vent exits through.
- Brace the vent pipe no more than 24 inches apart.
- In extremely cold climates, use an insulated chase that allows inspection of the vent pipe.
- Keep the termination away from shrubs, air conditioners, meters and recessed areas.
- Do not terminate above any door or window or under a deck.
- Seal the annular space around the penetration with approved material.
Applies to: Direct exhaust sidewall vent
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 86-87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.