Weil-McLain · Boiler troubleshooting

Direct exhaust sidewall termination location and length

Ultra Series 4

What is going on

Keep the vent exit where condensate, vapor and flue plume will not cause damage, injury or nuisance, and keep outside vent length within limits to avoid freezing.

Likely causes

  • Outside vent length too long, condensate freezes and shuts the boiler down
  • Termination above a door, window or deck
  • Termination over a public walkway

Check in this order

  1. Use a down-turned elbow that butts against the outside wall plate.
  2. Keep the total vent piping within the maximum length in Figure 12 (allows 2 elbows; reduce for more elbows).
  3. Keep exposed outside pipe to 4 feet or less without an enclosure; longer runs need an enclosure that the vent exits through.
  4. Brace the vent pipe no more than 24 inches apart.
  5. In extremely cold climates, use an insulated chase that allows inspection of the vent pipe.
  6. Keep the termination away from shrubs, air conditioners, meters and recessed areas.
  7. Do not terminate above any door or window or under a deck.
  8. Seal the annular space around the penetration with approved material.

Applies to: Direct exhaust sidewall vent

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 86-87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.