Viessmann · Boiler troubleshooting
Fixed high limit test, method 1 (boiler pump disconnected)
What is going on
Simulates an over-temperature condition to check the manual reset fixed high limit. Results in an F2 fault. Do not exceed the limit temperature.
Check in this order
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and gradually go into high fire.
- Once the burner ignites, carefully unplug the boiler pump plug from the control board.
- Watch the boiler temperature on the control display. It rises as heat goes into the heat exchanger, then the burner shuts off.
- Continue to observe. When the boiler reaches 210°F (99°C), the manual reset high limit trips and shows F2.
- If the limit is not reached, wait two minutes after burner shutoff, then briefly energize the boiler pump for no more than 1 second by reconnecting its plug. Repeat as needed.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352 (boiler sizes with flow switches may need the flow switch jumpered)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.