Viessmann · Boiler troubleshooting

Installation example: DHW storage tank with three zone circuits

Vitocrossal 300 CU3A

What is going on

Boiler with a DHW storage tank and three zone circuits. Zone 1 is switched from the boiler board, zones 2 and 3 use the AM1 extension module. Outdoor and DHW sensors are used.

Check in this order

  1. Wire the DHW pump to output 21 and the DHW recirculation pump to output 28/20.
  2. Connect the thermostats for zone circuits 1, 2 and 3 as dry contacts.
  3. Wire zone circuit 1 to output 157.
  4. Connect the AM1 extension module and wire zone circuit 2 to output A1 and zone circuit 3 to output A2.
  5. Install the outdoor temperature sensor and the DHW sensor.

Applies to: Vitocrossal 300 CU3A with DHW storage tank and three zone circuits

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A technical data manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.