Check flue gas temperature versus return temperature
What is going on
Flue gas should not run far above the boiler return temperature at high fire.
Likely causes
- Fouled heat exchanger
Check in this order
- Set the boiler to high fire.
- Use the control display to view flue gas temperature and boiler return temperature.
- Flue gas should be no more than 50°F above return temperature.
- If the difference is higher, clean the heat exchanger (see maintenance, p. 151).
- If the flue temperature is higher still, shut down, let cool, and clean the heat exchanger.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.