Weil-McLain · Boiler troubleshooting

Check flue gas temperature versus return temperature

ECO Tec Series 3

What is going on

Flue gas should not run far above the boiler return temperature at high fire.

Likely causes

  • Fouled heat exchanger

Check in this order

  1. Set the boiler to high fire.
  2. Use the control display to view flue gas temperature and boiler return temperature.
  3. Flue gas should be no more than 50°F above return temperature.
  4. If the difference is higher, clean the heat exchanger (see maintenance, p. 151).
  5. If the flue temperature is higher still, shut down, let cool, and clean the heat exchanger.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.