Changeover contact 66 for fault output or external boiler demand

Vitocrossal 200 CI2

What is going on

Contact 66 can report a fault or request heat from an external boiler. With supplemental enabled, it closes when full-load operation fails to reach setpoint for a set time.

Check in this order

  1. Set the function in parameter 1706.0 (Boiler group).
  2. Wire the fault or demand signal to contact 66 (NC, NO or COM as needed).
  3. Check the rated current of 2 A is not exceeded.

Applies to: Potential-free changeover contact 66

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.