Viessmann · Boiler troubleshooting

Check heating system, safety devices and water side

Vitorond 100

What is going on

Routine checks of pressure, relief valve, expansion tank, low water cut-off and pumps.

Check in this order

  1. Make sure all heating system and domestic hot water connections are pressure tight.
  2. Check the pressure gauge, air vent and pressure relief valve.
  3. Confirm the pressure relief valve does not leak and operates to the manufacturer's rating.
  4. Check the expansion tank, low water cut-off (if fitted) and pumps; follow the maintenance instructions supplied with each item.
  5. Flush float type low water cut-offs if used.
  6. With the system cold, confirm water fill pressure is between 10 and 15 psi. A lower reading usually means water loss.
  7. Repair all leaks. Follow the automatic fill valve instructions and local backflow preventer rules.
  8. Lubricate oil lubricated pumps.
  9. If an older non-diaphragm expansion tank is used, confirm the correct water level.

Applies to: VR1 40 to 63, 161 to 245

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 installation and service manual, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.