Connect combustion air damper (single boiler)

Vitotronic 100 GC1Vitotronic 300-K MW1S

What is going on

Wire a combustion air damper through the adaptor, with a field-supplied relay where the damper needs one.

Check in this order

  1. Disconnect power to the control and burner.
  2. Confirm the damper is suitable for this application and check its installation manual.
  3. Wire a 120 VAC field-supplied relay coil as shown in the diagram.
  4. Wire the damper end switch (120 VAC rated) to the normally open terminal on the adaptor board.
  5. Provide disconnect means and overcurrent protection as local codes require.
  6. Spring return dampers do not need the field relay.

Applies to: Single boiler with combustion air damper

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.