Dismantle the burner

Vitocrossal 300 CA3B

What is going on

Removing the upper burner section and then the burner tube assembly. A lifting device is needed for the burner.

Check in this order

  1. Close the gas shut-off valve and make sure the boiler is cold.
  2. Disconnect the burner gas line.
  3. Disconnect the connectors from the burner control unit.
  4. Pull off the ignition electrode connectors.
  5. Remove the 2 screws on the ignition electrode block and lift the block off.
  6. Remove the 6 nuts around the burner mounting plate.
  7. Remove the upper burner section.
  8. Secure the lifting chains at the 3 points on the upper burner frame.
  9. Remove the 8 nuts from the combustion chamber cover plate.
  10. Lift out the mounting plate with the burner tube using a lifting device.

Applies to: CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 70-71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.