Heating system piping, expansion tank and fill

NCB700

What is going on

Flush the whole system before connecting piping and keep debris out of the lines. Expansion tank and fill connection must be placed correctly.

Check in this order

  1. Flush the system to remove flux, solder, sediment and debris before connecting the boiler
  2. Clean the heating return strainer after the boiler is installed
  3. Size the expansion tank to the system water volume and fill pressure
  4. Connect the air separator to the expansion tank only if the separator is on the pump suction side
  5. Place the expansion tank and fill connection on the pump suction side
  6. Make sure the expansion tank cannot be isolated from the boiler while the system runs
  7. On diaphragm tanks, install an automatic air vent above the tank
  8. Repair leaks right away to avoid adding make-up water, which brings air and minerals into the system

Applies to: NCB700 space heating system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 184-187. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.